10~35kV Overhead Insulated Conductor
Product introduction
★ Product standard
This product is manufactured according to GB / t14049-2008 "rated voltage 10kV, 35kV overhead insulated cables" and iec60502 "rated voltage 1-30kv extruded insulated power cables and accessories".
★ Usage characteristics
2.1 rated voltage
2.2 the allowable long-term working temperature of cable conductor shall not exceed:
HDPE insulated overhead cable: 75 ℃;
XLPE insulated overhead cable: 90 ℃;
2.3 in case of short circuit (the longest duration shall not exceed 5S), the maximum allowable temperature of cable conductor shall not exceed:
HDPE insulated overhead cable: 150 ℃;
XLPE insulated overhead cable: 250 ℃;
2.4 the ambient temperature during cable laying shall not be lower than - 20 ℃.
2.5 allowable bending radius of cable:
Single core cable: no more than 20 times of the outer diameter of the cable.
Multi core cable: no more than 15 times of the outer diameter of the cable.
Model and name of cable
Model | Name | Application |
JKYJ | Copper core XLPE insulated overhead cable | This product is suitable for overhead power transmission lines with AC rated voltage U (UM) of 10 (12) kV and 35 (42) kV. |
JKTRYJ | XLPE insulated overhead cable with soft copper core | |
JKLYJ | Aluminum core XLPE insulated overhead cable | |
JKLGYJ | ACSR cored XLPE insulated overhead cable | |
JKLHYJ | Aluminum alloy core XLPE insulated overhead cable | |
JKY | Copper core polyethylene insulated overhead cable | |
JKTRY | Flexible copper core polyethylene insulated overhead cable | |
JKLY | Aluminum core polyethylene insulated overhead cable | |
JKLGY | ACSR PE insulated overhead cable | |
JKLHY | Aluminum alloy core polyethylene insulated overhead cable | |
JKLYJ/Q | Aluminum core light cross linked polyethylene insulated overhead cable | |
JKLHYJ/Q | Light weight XLPE insulated overhead cable with ACSR | |
JKLY/Q | Aluminum core light polyethylene thin insulation overhead cable | |
JKLHY/Q | Aluminum alloy core light polyethylene thin insulation overhead cable | |
JKLGY/Q | Light weight polyethylene thin insulated overhead cable with ACSR |
Scope of production
Model | Number of cores | Nominal cross section of conductor(mm2) | |
Rated voltage(KV) | |||
10 | 35 | ||
JKYJ、JKTRYJ、JKLYJ、JKLHYJ、JKLGYJ | 1 | 10~300 | 50~300 |
JKY、JKTRY、JKLY、JKLHY、JKLGY、JKLYJ/Q、 JKLHYJ/Q、JKLY/Q、JKLHY/Q、JKLGYJ/Q、JKLGY/Q |
1 | 10~300 | - |
Main technical parameters of cable
Material Science | Voltage level | Conductor temperature | Current carrying capacity correction factor at actual ambient temperature (℃) K | |||||||||
K V | ℃ | -5 | 0 | 5 | 10 | 15 | 20 | 30 | 35 | 40 | 45 | |
PE | 10 | 75 | 1.57 | 1.46 | 1.41 | 1.36 | 1.34 | 1.29 | 1.15 | 1.08 | 1.00 | 0.80 |
XLPE | 10 | 90 | 1.38 | 1.35 | 1.31 | 1.27 | 1.23 | 1.16 | 1.10 | 1.05 | 1.00 | 0.96 |
XLPE | 35 | 90 | 1.38 | 1.35 | 1.31 | 1.27 | 1.23 | 1.16 | 1.10 | 1.05 | 1.00 | 0.96 |
AC voltage test
Rated voltage | 10kV | 10kV | 35kV |
General structure insulated structure cable | Light cable with thin insulation structure | ||
Test voltage | 18kV/1min . No breakdown | 12kV/1min. No breakdown | 63kV/1min .No breakdown |
Cable operation conditions
1. Laying in air
1.1 when the single core cable is laid in parallel, the center distance: 185 mm 2 or less is twice of the cable diameter, and 240mm 2 or more is 90mm.
1.2 ambient air temperature: 40 ℃
1.3 long term maximum operating temperature of Conductor: 90 ℃
2. Directly buried laying
2.1 When the single core cable is laid without contact, the distance between the center of the cable is twice the diameter of the cable.
2.2 soil temperature: 25 ℃
2.3 long term maximum working temperature of Conductor: 90 ℃
2.4 soil temperature coefficient: 1.0 ℃. M / W
2.5 direct burial depth: 0.7m
Cable installation and use
1. Cable selection
1.1 the rated voltage U0 / u (UM) of the cable is shown as: uo is the rated power frequency voltage between the conductor for the cable design and the ground or metal shield, u is the rated power frequency voltage between the conductors for the cable design, and um is the maximum value of the highest system voltage that the equipment can withstand.
1.2 according to the different laying environment and load of the cable, correctly design and select the type and specification of the cable. Non armored type is suitable for overhead, indoor, tunnel, cable trench and other occasions, and can not bear external mechanical force; The armored type can be directly buried underground under the same conditions as the non armored type, and can bear certain external mechanical force. Single core cable is not allowed to be laid in magnetic pipe. Special type of cable should be selected for inflammable and explosive, chemical corrosive, high temperature and low temperature.
2. Storage and transportation
During the storage of cables, the packaging shall be standardized to avoid long-term outdoor sun exposure, both ends shall be reliably sealed, long-term storage and humid environment are not allowed, and the cable reel cannot be placed horizontally. During transportation, the height of the plate should be considered and fixed effectively. During hoisting, several plates are not allowed to be hoisted at the same time, and it is strictly forbidden to push down from a high place.
3. Laying and installation
3.1 special tools such as pay off rack and guide roller shall be used for cable laying to prevent mechanical damage and keep away from heat source.
3.2 when the cable is laid through the pipe, the inner diameter of the pipe shall not be less than 1.5 times of the outer diameter of the cable. When multiple cables are laid through the pipe, it is forbidden to twist and squeeze the cable. The pipe has enough capacity, and the total area of the cable shall not exceed 40% of the total area in the pipe
3.3 the minimum temperature of cable laying shall not be lower than 0 ℃, and the bending radius shall not be less than 20 times.
3.4 when the traction conductor clamp is used for laying, the maximum allowable traction force is p = OA (n), a conductor section. O is 50N / mm2 (copper) and 30n / mm2 (aluminum).
4. Test
After installation, the insulation resistance of the cable shall be tested without load. If necessary, AC power frequency withstand voltage test shall be conducted for 1min